Skip to main content
Siemens 5SY5210-7CC11 — 2-Pole MCB (DIN Rail)

Siemens 5SY5210-7CC11 SENTRON MCB, 2P C-curve 10A DC 440V

MPN5SY5210-7CC11

Siemens SENTRON 5SY5210-7CC11, 2-pole miniature circuit breaker, C-curve 10 A at 35 °C, DC 440 V, 10 kA breaking capacity per IEC 60947-2, railway-certified, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY5210-7CC11 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentRailway
5SY5210-7CC11 — Electrical
ParameterValue
Number of poles2
5SY5210-7CC11 — Protection
ParameterValue
Tripping characteristic classC
Overvoltage categoryIII
5SY5210-7CC11 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY5210-7CC11 — Environmental
ParameterValue
Pollution degree3

Product details

At 40 °C the continuous rating derates to 9.25 A, at 50 °C to 8.43 A, and at 60 °C to 7.52 A — a critical derating curve for sealed enclosures or high-ambient railway cabinets.

Railway certification and environmental range

This MCB is explicitly designed for railway applications and carries vibration resistance per IEC 60068-2-6: ±1 mm at 5 to 25 Hz, 50 m/s² at 25 to 150 Hz. Ambient temperature range spans -40 °C to 75 °C, with humidity influence capped at 95% up to 55 °C, 55% up to 70 °C, and 35% at 75 °C. The lifecycle status is current production.

Width is 36 mm (2 modular units), depth 76 mm, height 90 mm, installation depth 70 mm. Fastens via the quick assembly system in any mounting position. Combined top and bottom terminals simplify daisy-chaining. Halogen-free and silicon-free construction.

Frequently asked questions

What is the DC voltage and breaking capacity of 5SY5210-7CC11?

Rated DC voltage is 440 V with a breaking capacity of 10 kA per IEC 60947-2.

Is 5SY5210-7CC11 suitable for railway applications?

Yes, it is designed for railway operation and tested to vibration resistance per IEC 60068-2-6.

Where can I buy 5SY5210-7CC11 and what is the lead time?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
5SY5210-7CC11