Ratings that matter for fit
The 13 A rating is at 35 °C ambient; the breaker derates to 12.38 A at 40 °C and 11.39 A at 60 °C. If your panel runs warm — say, a sealed enclosure in a washdown area — use the 40 °C or 50 °C column for sizing. The 2-pole design switches both phase and neutral (no neutral conductor switching, so both poles are protected).
This is an active, in-production Siemens SENTRON MCB.