Rated breaking capacity is 10 kA per IEC/EN 60898-2 and UL1077, and 15 kA per IEC 60947-2 at DC — so it handles fault currents typical of sub-distribution boards in commercial buildings and light industrial panels. This 2-pole unit switches both phase and neutral? No — neutral conductor switching is not provided. It's a 2-pole overcurrent device for double-pole protection on single-phase or DC circuits. Operating voltage: 400 V AC, 440 V DC (max 500 V DC). Frequency 50/60 Hz.
Mounting & Panel Fit
At 36 mm wide (2 MW) and 76 mm deep, it fits standard distribution boards and sub-panels. Sealable for tamper-proof installations. Halogen-free and silicon-free construction suits sensitive environments like data centers or medical facilities.
Rated for ambient temperatures from -40 °C to +75 °C, with humidity derating: max 95% RH up to 55 °C, 55% up to 70 °C, 35% up to 75 °C. Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz.