Siemens 5SY5216-7CC12 — 2-Pole MCB (DIN Rail)

Siemens 5SY5216-7CC12 MCB, 2P C16, 440V DC, 10kA

MPN5SY5216-7CC12

Siemens 5SY5 series, MCB, 2-pole C16, 440V DC, 10kA breaking capacity, order code 5SY5216-7CC12.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Product details

The Siemens 5SY5216-7CC12 is a 2-pole miniature circuit breaker (MCB) from the 5SY5 series, rated C16 with a 10 kA breaking capacity at 440 V DC. It is designed for DC branch-circuit protection in control panels, switchgear, and distribution boards where a compact, DIN-rail-mount breaker is specified.

The C16 trip curve means the breaker holds 1.13× to 1.45× rated current (18.1 A to 23.2 A) for over an hour, then trips magnetically between 5× and 10× In (80 A to 160 A). This suits motor-starting or moderate inrush loads where a B-curve would nuisance-trip but a D-curve would delay too long. The 2-pole configuration (2P) switches both the positive and negative conductors in a DC circuit, providing full isolation. This is standard for ungrounded DC systems or where double-pole disconnection is required by code.

Deployment Context

Snaps onto standard 35 mm DIN rail per EN 60715, fitting into a 36 mm-wide module (2 × 18 mm pole spacing). In a panel, account for the 10 kA SCCR when sizing the upstream bus and ensuring the enclosure short-circuit rating matches.

Frequently asked questions

Where can I buy the 5SY5216-7CC12 and get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote to confirm current availability and pricing.

What is the breaking capacity of the 5SY5216-7CC12?

It has a 10 kA breaking capacity at 440 V DC, as specified in the description MCB 5SY5 CRH 440V DC 10KA 2P C16.

MPN
5SY5216-7CC12