Skip to main content
Siemens 5SY5216-7KK11

Siemens 5SY5216-7KK11 SENTRON MCB, 2P C-curve 16A, 10kA

MPN 5SY5216-7KK11

Siemens SENTRON 5SY5216-7KK11, 2-pole miniature circuit breaker, C-curve, 16 A rated current (35 °C), 10 kA breaking capacity per EN 60898, 2 MW width, IP20.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SY5216-7KK11 specifications
ParameterValue
Poles2
IP ratingIP20
MountingQuick assembly system
Temp operating max75 °C
Temp operating min55 °C
Depth76 mm
Width36 mm
Height90 mm
Energy limitation class3

Product details

Siemens 5SY5216-7KK11 — SENTRON 2P C-curve MCB, 16 A, 10 kA

The Siemens 5SY5216-7KK11 is a SENTRON miniature circuit breaker (MCB) in a 2-pole, C-curve configuration rated at 16 A (at 35 °C) with a 10 kA breaking capacity per EN 60898. The 10 kA interrupting rating at 230/400 V AC covers most commercial and light-industrial fault levels; for DC circuits it also holds 10 kA per EN 60898-2.

Thermal derating and ambient limits

Rated current is 16 A at 35 °C, but drops to 15.02 A at 40 °C, 14.51 A at 45 °C, 13.98 A at 50 °C, 13.44 A at 55 °C, and 12.86 A at 60 °C. If the panel ambient runs warm — say, a crowded enclosure near a drive cabinet — size the load to the derated figure at your actual ambient, not the 35 °C headline.

Snap-on DIN rail mount (quick-assembly system), any orientation. The 2-pole body is 36 mm wide (2 MW), 90 mm tall, 76 mm deep with an installation depth of 70 mm.

It is designed for railway applications per its product designation. The manufacturer provides standard compliance documentation (RoHS, REACH, IEC/EN 60898) — available on request with the RFQ.

MPN