What this 2-pole B-curve MCB does in your panel
It's listed under UL1077 as a supplementary protector, so it fits North American panels as a branch-circuit component, not a service-entrance breaker. Two modular width units (36 mm) snap onto DIN rail; the quick-assembly fastening and combined top/bottom terminals speed up panel wiring.
Environmental and compliance details
Operating temperature range from -40 °C to 75 °C, with derating above 55 °C per the humidity table (max 95% RH at 55 °C, tapering to 35% at 75 °C). Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz. Sealable with a lockable cover for tamper-proof installations.