Siemens 5SY5220-6CC11 — 2-Pole MCB (DIN Rail)

Siemens 5SY5220-6CC11 SENTRON MCB, 2P B 20A DC 440V

MPN5SY5220-6CC11

Siemens SENTRON 5SY5220-6CC11 miniature circuit breaker, 2-pole, B-curve, 20 A, DC 440 V, 10 kA per IEC 60947-2, for railway applications.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY5220-6CC11 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
5SY5220-6CC11 — Electrical
ParameterValue
Number of poles2
5SY5220-6CC11 — Protection
ParameterValue
Tripping characteristic classB
Overvoltage categoryIII
5SY5220-6CC11 — Mechanical
ParameterValue
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Protection degree (IP)IP20, with connected conductors

Product details

Unlike AC, a DC arc does not self-extinguish at zero-crossing, so the breaker must force the arc out magnetically. This unit is rated to interrupt a 10 kA prospective fault current at 440 V DC — sufficient for most 400 V DC drives, UPS, and railway auxiliary supplies. The maximum DC voltage of 500 V gives headroom on a 440 V nominal rail. For a 20 A DC circuit feeding control transformers, solenoids, or resistive heater banks, B is appropriate.

Frequently asked questions

What is the wire range for the terminals on 5SY5220-6CC11?

Solid and stranded conductors from 0.75 mm² up to 35 mm². Tightening torque 2.5–3.5 N·m.