Skip to main content
Siemens 5SY5263-7KK11 — 2-Pole MCB (DIN Rail)

Siemens 5SY5263-7KK11 SENTRON MCB, 2-Pole C-Curve 63A 400V A

MPN5SY5263-7KK11

Siemens SENTRON 5SY5263-7KK11 miniature circuit breaker, 2-pole, C-curve, 63 A rated current, 400 V AC / 440 V DC, 10 kA breaking capacity, IP20, railway design.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SY5263-7KK11 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentuniversal current
5SY5263-7KK11 — Electrical
ParameterValue
Number of poles2
5SY5263-7KK11 — Protection
ParameterValue
Tripping characteristic classC
Overvoltage categoryIII
5SY5263-7KK11 — Mechanical
ParameterValue
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY5263-7KK11 — Environmental
ParameterValue
Pollution degree3

Product details

Integrator's field note

The Siemens SENTRON 5SY5263-7KK11 is a 2-pole miniature circuit breaker rated 63 A at 400 V AC (C-curve, 10 kA per EN 60898) and 440 V DC (10 kA per EN 60898-2). Universal-current design means it handles both AC and DC circuits, but observe DC polarity at the terminals (AC as required, DC polarity must be followed).

Halogen-free and silicon-free construction. Ambient operating range -40 °C to 75 °C, with derating per the influence curve (max 95% RH at 55 °C, 55% at 70 °C, 35% at 75 °C). Designed for railway applications (energy limiting class 3). Sealable for tamper-proof installations. Touch protection included.

Frequently asked questions

What is the breaking capacity of 5SY5263-7KK11?

10 kA at 400 V AC per EN 60898, and 10 kA at DC per EN 60898-2.

What compliance documentation does Siemens provide for 5SY5263-7KK11?

The part is designed per EN 60898 (AC) and EN 60898-2 (DC), with functional classification per DIN EN 61346-2 and DIN EN 81346-2. Halogen-free and silicon-free construction supports environmental compliance requirements.

Where can I buy 5SY5263-7KK11?