It carries an 880 V DC rated voltage (1000 V DC maximum) and a 10 kA DC breaking capacity tested to IEC 60947-2 — the standard for industrial DC fault interruption.
Four poles in a 72 mm wide housing (4 width units at 18 mm each) snap onto the DIN rail via the quick-assembly system and accept conductors from 0.75 to 35 mm² solid or stranded. The combined terminal at top and bottom simplifies daisy-chaining the DC bus. Installation depth is 70 mm plus the 76 mm overall depth; plan for finger clearance on the toggle and the sealable cover if the panel door closes tight.