Skip to main content
Siemens 5SY5410-7CC — 4-Pole MCB (DIN Rail)

Siemens 5SY5410-7CC SENTRON MCB, 4P C-curve 10A DC 880V

MPN5SY5410-7CC

Siemens SENTRON 5SY5410-7CC, 4-pole miniature circuit breaker, C-curve, 10 A at 35 °C, DC 880 V, 10 kA breaking capacity.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY5410-7CC — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY5410-7CC — Ratings
ParameterValue
Number of poles4
Pole configuration4P
5SY5410-7CC — Protection
ParameterValue
Tripping characteristic (trip curve)C
Overvoltage categoryII
Pollution degree2
Degree of protection (IP)IP20, with connected conductors
Touch protectionYes
5SY5410-7CC — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Fastening / mounting methodQuick assembly system
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SY5410-7CC — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C

Product details

The Siemens 5SY5410-7CC is a SENTRON miniature circuit breaker — 4-pole, C-curve, rated 10 A at 35 °C, designed for DC circuits up to 880 V with a breaking capacity of 10 kA per IEC 60947-2.

The 10 A rating at 35 °C derates to 9.32 A at 40 °C, 8.96 A at 45 °C, 8.58 A at 50 °C, and 8.19 A at 55 °C — if your panel ambient runs warm, size the upstream protection for the derated value, not the nominal. Vibration resistance per IEC 60068-2-6 (±1 mm at 5 to 25 Hz, 50 m/s² at 25 to 150 Hz) means it survives on a machine frame or conveyor line.

Panel fit and compliance notes

The 4-pole design does not switch the neutral (no neutral conductor switching). It is halogen-free and silicon-free — relevant for clean-room or food-and-bev lines where outgassing matters. Sealable terminals are present if your site requires tamper-proofing after commissioning. The combined terminal design (top and bottom) accepts standard screw-clamp wiring. Polarity must be observed on the DC supply cord — this is a polarized breaker. Touch protection is built in, so live parts are not exposed when the breaker is mounted in the panel.

Frequently asked questions

Where can I buy 5SY5410-7CC and what is the lead time?

This part is sourced and quoted to order through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead time and price.

What is the closest functional second-source for 5SY5410-7CC?

The closest functional peer is 5SY5416-7 — same 4-pole C-curve SENTRON family, same DC 880 V and 10 kA breaking capacity, but rated 16 A at 35 °C instead of 10 A. It drops into the same DIN-rail footprint (4 MW) without rewiring, but the higher current rating changes the protection coordination. Use it only if your load actually draws 16 A.

Will 5SY5410-7CC drop into a panel specified around 5SY5416-7 without rewiring?

Yes — both are 4-pole, 4 MW wide, same depth 76 mm, same quick-assembly DIN-rail mount. The physical swap is direct. The difference is the current rating: 10 A vs 16 A. If the panel was wired for a 16 A load, the 10 A breaker will trip on that load. Verify the actual load current before swapping.

What compliance documentation does Siemens provide for 5SY5410-7CC?

The part is designed per IEC 60947-2 (DC breaking capacity 10 kA at 880 V) and carries the SENTRON brand. It is halogen-free and silicon-free. For specific RoHS, REACH, UL, or IEC declarations, request the manufacturer's compliance pack at quote time — it is typically available as a PDF with the shipment.

MPN
5SY5410-7CC