Siemens 5SY5413-6 — 4-Pole MCB (DIN Rail)

Siemens 5SY5413-6 SENTRON MCB, 4P B-Curve 13A 10kA

MPN5SY5413-6
Active

Siemens SENTRON 5SY5413-6, 4-pole miniature circuit breaker, B-curve, 13 A rated at 35 °C, 10 kA breaking capacity per EN 60898, 4 MW width.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY5413-6 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityuniversal current
5SY5413-6 — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated current (In), AC13 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, AC (single-phase)440 V
5SY5413-6 — Protection
ParameterValue
Tripping characteristic (trip curve)B
Rated breaking capacity (Icn), per EN 6089810 kA
Energy limitation class3
Overvoltage categoryII
Pollution degree2
Degree of protection (IP)IP20, with connected conductors
Touch protectionYes
5SY5413-6 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Fastening / mounting methodQuick assembly system
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SY5413-6 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
5SY5413-6 — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)10 000

Product details

The 5SY5413-6: The 13 A rating at 35 °C is the baseline; the datasheet provides a full derating curve — 12.38 A at 40 °C, 12.05 A at 45 °C, 11.73 A at 50 °C, 11.38 A at 55 °C, and 11.02 A at 60 °C. If the breaker lives in a warm enclosure, size up one step or verify the actual ambient against these numbers. For motor or high-inrush loads, a C or D curve would be a better fit. For DC circuits, the same 10 kA applies per EN 60898-2. The 4-pole design (4P) switches all four conductors — three phases plus neutral. This is typical for three-phase loads where the neutral must be switched for isolation, or for TT/TN-S systems where neutral protection is required. The sealable feature (padlockable toggle) allows lockout/tagout per safety procedures.

Deployment context

The breaker carries a degree of pollution 2 rating and overvoltage category II. The product designation per IEC 81346-2 is function code F (protection device).

Frequently asked questions

What is the breaking capacity of 5SY5413-6?

10 kA per EN 60898 for AC circuits, and 10 kA per EN 60898-2 for DC circuits.

Where can I buy 5SY5413-6?

Sourced and quoted to order against an RFQ through independent distribution channels. Price and availability are confirmed at quote time.

Will 5SY5413-6 drop into a panel specified around 5SY5416-7 without rewiring?

Both are 4-pole SENTRON MCBs in the same 4 MW footprint (72 mm wide), so the mechanical fit is identical. The difference is the trip curve and rating: 5SY5413-6 is a 13 A B-curve; 5SY5416-7 is a different rating/curve. If the circuit design requires a B-curve at 13 A, the swap is direct. If the original spec called for a different curve or ampacity, verify before substitution.

What compliance documentation does Siemens provide for 5SY5413-6?

The part is designed to EN 60898 and EN 60898-2, carries a pollution degree 2 and overvoltage category II rating, and is halogen-free and silicon-free. Full RoHS/REACH/UL/IEC declarations are available from the manufacturer upon request.

MPN
5SY5413-6