Skip to main content
Siemens 5SY5416-6CC — 4-Pole MCB (DIN Rail)

Siemens 5SY5416-6CC SENTRON MCB, 880V DC, 10kA, 4P, B, 16A

MPN5SY5416-6CC

Siemens SENTRON 5SY5CC series, miniature circuit breaker, 880 V DC, 10 kA (IEC 60947-2), 4-pole, B characteristic, 16 A.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY5416-6CC — Identification
ParameterValue
Type / order code5SY5CC
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY5416-6CC — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated voltage, DC (max.)1 000 V
Voltage typeDC
5SY5416-6CC — Protection
ParameterValue
Tripping characteristic (trip curve)B
Breaking capacity, AC (UL 1077 / CSA C22.2 No.235)5 kA
Overvoltage categoryII
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingNo
Touch protectionYes
5SY5416-6CC — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
SealableYes
5SY5416-6CC — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C

Product details

The Siemens SENTRON 5SY5416-6CC is a 4-pole DC miniature circuit breaker rated 880 V with a 10 kA breaking capacity per IEC 60947-2. Polarity matters on this design; the evidence flags it explicitly, so the line and load sides must be wired consistently.

That's the SCCR your DC bus needs to withstand. The AC rating of 5 kA per UL 1077 and CSA C22.2 No.235 covers installations where the same part sees AC supply, though the primary duty here is DC. Conductor termination accepts 0.75 to 35 mm² solid or stranded, with a tightening torque of 2.5 to 3.5 N·m (22 to 31 lbf·in). Mounting uses the quick assembly system — snaps onto a DIN rail without tools. Storage range extends to -40 to +75 °C.

The breaker carries IEC 60947-2 and UL 1077 / CSA C22.2 No.235 certifications.

Frequently asked questions

Where can I buy 5SY5416-6CC and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of 5SY5416-6CC at DC?

10 kA at 880 V DC per IEC 60947-2. It also carries a 5 kA AC rating per UL 1077 and CSA C22.2 No.235.

What conductor sizes does the 5SY5416-6CC accept?

Solid or stranded conductors from 0.75 to 35 mm². The terminal torque range is 2.5 to 3.5 N·m (22 to 31 lbf·in).

Does 5SY5416-6CC require polarity consideration?

Yes, the evidence specifies that polarity must be considered when connecting the power supply cord.

MPN
5SY5416-6CC