What this 4-pole C-curve MCB delivers
The 4-pole design switches all four conductors — three phases plus neutral — though neutral is not switched separately (no neutral conductor switching).
The IP20 rating applies only with connected conductors; the front sealable cover (yes, sealable) allows lockout/tagout on the panel door. Combined top and bottom terminals simplify busbar wiring in a distribution board.
Operating temperature range is -40 °C to +75 °C, with humidity limits: 95% RH up to 55 °C, 55% RH up to 70 °C, 35% RH up to 75 °C. Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz. Pollution degree 2, overvoltage category II.