It carries a 10 kA interrupting capacity per IEC/EN 60898-2 at 400 V AC, and a 15 kA rating per IEC 60947-2 at DC — the higher DC figure matters for panels with battery-backed or rectified supplies, where fault currents can be sustained longer than in AC circuits.
Panel fit and environmental range
Width is 72 mm (4 modular units), depth 76 mm, height 90 mm. Operating temperature spans -40 °C to 75 °C, with humidity derating above 55 °C: max 95% RH at 55 °C, dropping to 35% at 75 °C. That -40 °C floor means it's usable in unheated outdoor cabinets or cold-storage environments without a heater.
Listed to IEC/EN 60898-2 and UL1077, with overvoltage category II and pollution degree 2.