Skip to main content
Siemens 5SY5463-6 — 4-Pole MCB (DIN Rail)

Siemens 5SY5463-6 SENTRON MCB, 4P B-Curve, 10 kA, 400 V AC

MPN5SY5463-6
Active

Siemens SENTRON 5SY5463-6, 4-pole miniature circuit breaker, B-curve, 10 kA per IEC/EN 60898-2, rated 400 V AC / 880 V DC, UL1077 listed, IP20.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

5SY5463-6 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityuniversal current

Ratings

5SY5463-6 — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated voltage, AC (multi-phase)440 V

Protection

5SY5463-6 — Protection
ParameterValue
Tripping characteristic (trip curve)B
Energy limitation class3
Overvoltage categoryII
Pollution degree2
Degree of protection (IP)IP20, with connected conductors

Mechanical

5SY5463-6 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Fastening / mounting methodQuick assembly system
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes

Environmental

5SY5463-6 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C

Performance

5SY5463-6 — Performance
ParameterValue
Power loss per pole, AC (hot state, at In)6 W

Product details

What the B-curve and breaking capacity mean for your panel

The Siemens 5SY5463-6 is a 4-pole SENTRON miniature circuit breaker with a B-curve trip characteristic — it trips between 3 and 5 times rated current, which makes it the standard choice for resistive and general-purpose loads where inrush is modest (lighting, heaters, control transformers). The 10 kA breaking capacity per IEC/EN 60898-2 tells you it can safely interrupt a fault current up to that level at 400 V AC without welding contacts or cascading upstream. That same 10 kA holds for DC circuits per EN 60898-2, and the part is also rated 15 kA at DC per IEC 60947-2 — a useful headroom if your DC bus is stiff. Rated operating voltage is 400 V AC (multi-phase or single-phase) and 880 V DC, with a maximum DC voltage of 1 000 V. That DC rating is unusual for a 4-module-width MCB — it covers battery banks, UPS systems, and solar combiner boxes where the string voltage runs high. The part is universal-current rated (AC/DC) so you don't need a separate DC-specific breaker for mixed panels.

Physical fit and panel integration

The breaker occupies 4 modular width units (72 mm) on a DIN rail, with a depth of 76 mm and an installation depth of 70 mm. It mounts in any position and uses the quick-assembly system — clips onto the rail without tools. The IP20 rating applies with connected conductors, so it's standard for enclosed distribution boards. Vibration resistance per IEC 60068-2-6 covers ±1 mm at 5–25 Hz and 50 m/s² at 25–150 Hz, which is enough for most industrial panels unless you're mounting directly on a high-vibration pump skid.

Approvals and compliance

The 5SY5463-6 is certified to IEC/EN 60898-2 and UL1077, which means it's accepted in both IEC and North American panels (UL 1077 is the supplementary protector standard). It's halogen-free and silicon-free, so it won't outgas corrosive compounds in a sealed enclosure. The sealable design allows the installer to lock the toggle position — useful for lockout/tagout procedures on critical circuits.

Frequently asked questions

Where can I buy the 5SY5463-6 and how is it quoted?

We source the 5SY5463-6 through independent distribution and quote it to order against an RFQ. Availability and current pricing are confirmed at quote time.

What is the 5SY5463-6's depth?

The depth is 76 mm, with an installation depth of 70 mm.

What compliance documentation does the 5SY5463-6 carry?

It is certified to IEC/EN 60898-2 and UL1077, and is halogen-free and silicon-free.