Skip to main content
Siemens 5SY6004-7KL — 1-Pole MCB (DIN Rail)

Siemens 5SY6004-7KL SENTRON MCB, 1P+N, C Curve, 4 A, 6 kA

MPN5SY6004-7KL

Siemens SENTRON 5SY6004-7KL miniature circuit breaker, 1P+N, C curve, 4 A rated current, 6 kA breaking capacity at 230 V AC, 1 MW wide, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY6004-7KL — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
5SY6004-7KL — Electrical & Protection
ParameterValue
Tripping characteristic classC
Rated value (EN 60898)6 kA
Energy limitation class3
Overvoltage categoryIII
5SY6004-7KL — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodstandard rail
Combined terminal, topNo
Combined terminal, bottomNo
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY6004-7KL — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

The C curve means the magnetic trip operates at 5 to 10 times rated current (20–40 A for this 4 A unit), making it suitable for loads with moderate inrush — lighting banks, small transformers, or motorized valves. The 1 MW width (18 mm) is the standard single-module footprint, so it occupies one position on the DIN rail. The IP20 rating applies only when conductors are connected — the front face is touch-protected per the product feature, but the terminals are not sealed against dust ingress.

Integration notes

The supply can be fed from either end (top or bottom) — the position of the power supply cord is unrestricted. The neutral conductor is switched internally; no external neutral link is required.

Frequently asked questions

What is the breaking capacity of 5SY6004-7KL?

6 kA at 230 V AC per EN 60898, which is the standard rating for final subcircuit protection in residential and light commercial panels.

What is the difference between 5SY6004-7KL and 5SY6002-7KL?

The only difference is the rated current: 5SY6004-7KL is 4 A, while 5SY6002-7KL is 2 A. Both are 1P+N, C curve, 6 kA, 1 MW wide, and share the same physical dimensions and environmental ratings. They are direct drop-in replacements for each other in the same panel position, provided the load current matches.

Where can I buy 5SY6004-7KL?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What compliance documentation does Siemens provide for 5SY6004-7KL?

The part carries the SENTRON brand and is designed to meet EN 60898, IEC 60947-2, and UL 1077 standards. It is halogen-free and silicon-free. Specific declarations (RoHS, REACH, CE, UKCA) are available from the manufacturer upon request.

MPN