The SENTRON 5SY6013-7KV is a 1+N-pole miniature circuit breaker with C-curve tripping characteristic, rated 13 A at 230 V AC and a breaking capacity of 6 kA per EN 60898.
The 1+N-pole design switches both phase and neutral, with the neutral pole breaking after the phase pole and remaking before it — a requirement in many national wiring regulations for final circuits. Rated insulation voltage (Ui) is 250 V AC, and the overvoltage category is III, suitable for fixed-installation distribution boards. The breaker derates at elevated temperatures (12.35 A at 40 °C, 12.09 A at 45 °C), so for continuous full-load use at the rated 13 A, ambient should stay at or below 30 °C.
Installation depth is 70 mm; dimensions are 18 mm wide × 90 mm high × 76 mm deep. Touch protection is provided. The supply cord position is any — no restriction on top or bottom feed. Mechanical service life is typically 10,000 switching cycles.