Skip to main content
Siemens 5SY6032-6KL — 1-Pole MCB (DIN Rail)

Siemens 5SY6032-6KL SENTRON MCB, 1P+N, B Curve, 32 A, 6 kA

MPN5SY6032-6KL

Siemens SENTRON 5SY6032-6KL, miniature circuit breaker, 1P+N, B characteristic, 32 A rated current, 6 kA breaking capacity at 230 V AC per EN 60898.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY6032-6KL — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
5SY6032-6KL — Electrical & Protection
ParameterValue
Tripping characteristic classB
Rated value (EN 60898)6 kA
Overvoltage categoryIII
5SY6032-6KL — Mounting & Connection
ParameterValue
Mounting positionany
Combined terminal, topNo
Combined terminal, bottomNo
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Torque, min.24 V
SealableYes
5SY6032-6KL — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SY6032-6KL is a 1P+N miniature circuit breaker from the SENTRON family, rated 32 A with a B tripping characteristic and a 6 kA breaking capacity per EN 60898 at 230 V AC. It switches both the phase and neutral, with the neutral on the left side of the unit. Mounts on standard DIN rail, takes up one width unit (18 mm), and can be installed in any position. The screw terminals accept solid or stranded copper from 0.75 mm² up to 16 mm², with a recommended tightening torque of 2 to 2.5 N·m. That's enough wire range for a 32 A circuit feeding a submains or a heavy appliance feed.

If you're dealing with higher inrush (transformers, larger motors), a C-curve sibling would be the better call; this one is for the standard final-circuit duty. Energy limiting class 3 means it restricts let-through energy well during a fault, which helps with downstream coordination and reduces arc-flash stress on the conductors. The overvoltage category III rating confirms it's intended for fixed-installation distribution boards, not for equipment-level protection.

Installation notes from the field

That matters when you're laying out a distribution board: the feed order is fixed, and you can't swap phase and neutral positions. Touch protection is built into the terminals per the product feature. Halogen-free and silicon-free construction — no problematic outgassing in confined spaces or near sensitive contacts. IP20 rating applies with conductors connected, so the panel itself provides the environmental seal.

Frequently asked questions

What wire sizes does the 5SY6032-6KL accept?

The screw terminals accept solid or stranded copper from 0.75 mm² up to 16 mm². Tightening torque is 2 to 2.5 N·m (17.7 to 22.1 lbf·in).

Does the 5SY6032-6KL switch the neutral?

Yes, it is a 1P+N breaker that switches both the phase and the neutral conductor. The neutral terminal is on the left side of the unit.

MPN
5SY6032-6KL