The SENTRON 5SY6032-6KV is a 1+N-pole miniature circuit breaker rated 32 A with a B tripping characteristic and 6 kA breaking capacity at 230 V AC per EN 60898.
The 1+N-pole configuration switches both line and neutral, which is required in some regional wiring codes (UK, Australia, parts of Europe) to guarantee isolation on both conductors.
The 70 mm installation depth matches the SENTRON 5SY series footprint — no extra clearance needed behind the panel door beyond what a typical MCB already requires. Ambient temperature range is -25 to +45 °C, with periodic exposure up to +55 °C and 95% humidity; derating applies above 40 °C per the thermal curve in the datasheet. Screw terminals accept 0.75–16 mm² solid or stranded copper, torqued to 2–2.5 N·m (17.7–22.1 lbf·in).