Siemens 5SY6032-7 — 1-Pole MCB (DIN Rail)

Siemens SENTRON 5SY6032-7 MCB, 1P+N, C 32 A, 6 kA

MPN5SY6032-7

Siemens SENTRON 5SY6032-7 miniature circuit breaker, 1P+N, C-curve 32 A, 6 kA breaking capacity per EN 60898, 230 V AC, 1 MW wide, current lifecycle stage.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY6032-7 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
5SY6032-7 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Rated value (EN 60898)6 kA
Energy limitation class3
Overvoltage categoryIII
5SY6032-7 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodstandard rail
Combined terminal, topNo
Combined terminal, bottomNo
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY6032-7 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens SENTRON 5SY6032-7 is a 1P+N miniature circuit breaker (MCB) with a C-curve tripping characteristic rated 32 A at 30 °C, per EN 60898. It switches the neutral conductor along with the line, so a single-pole isolation is enough for the circuit — no separate neutral block needed.

IP20 with connected conductors — normal for a distribution board; keep it behind a panel door or cover.

Derating and ambient conditions

Rated 32 A at 30 °C; derates to 30.4 A at 40 °C and 29.76 A at 45 °C. If your enclosure runs hot — say a tightly packed sub-distribution board — factor that drop. Halogen-free and silicon-free construction; sealable for tamper-evident applications.

Frequently asked questions

Where can I buy 5SY6032-7 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm availability and current pricing — no stock count or price is published here.

What is 5SY6032-7's listed depth (76 mm) on this component line?

The depth is 76 mm, with an installation depth of 70 mm. Width is 18 mm (1 MW), height 90 mm.

What compliance documentation does this brand provide for 5SY6032-7 (RoHS, REACH, UL, IEC)?

The part is designed to EN 60898 (breaking capacity 6 kA) and carries IEC 81346-2 designation code F. It is halogen-free and silicon-free. For specific RoHS/REACH/UL declarations, request the manufacturer's compliance documentation at quote time — the evidence here confirms the EN and IEC standards but not each certificate.

MPN