The neutral pole switches with the line pole, so you get full isolation on both conductors when the breaker trips or is manually opened.
At 18 mm wide (1 width unit), it occupies a single module slot — no extra space needed for the switched neutral. Accepts solid or stranded conductors from 0.75 to 16 mm²; screw terminals with a tightening torque of 2 to 2.5 N·m (17.7–22.1 lbf·in). Strip length and ferrule sizing follow standard practice for that cross-section range. Mounting position is unrestricted, and the power supply cord can enter from any side. Installation depth is 70 mm; the overall depth of the device is 76 mm.
Rated for ambient temperatures from -25 to +45 °C, with periodic excursions to +55 °C and up to 95% humidity. Storage range is -40 to +75 °C. Vibration-resistant per IEC 60068-2-6.
This 5SY6032-7KL is a current-production part. The sealable feature (tamper-proof cover option) is useful for installations that require lockout/tagout or anti-tamper compliance.