Siemens 5SY6040-7 — 1-Pole MCB (DIN Rail)

Siemens 5SY6040-7 SENTRON MCB, 40A C-Curve 1P+N 6kA

MPN5SY6040-7

Siemens SENTRON 5SY6040-7 miniature circuit breaker, 40 A, C-curve, 1P+N, 6 kA per EN 60898, 230 V AC, 18 mm wide.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY6040-7 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
5SY6040-7 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Rated value (EN 60898)6 kA
Energy limitation class3
Overvoltage categoryIII
5SY6040-7 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodstandard rail
Combined terminal, topNo
Combined terminal, bottomNo
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY6040-7 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens SENTRON 5SY6040-7 is a 1P+N miniature circuit breaker rated 40 A with a C-curve trip characteristic, breaking 6 kA per EN 60898 at 230 V AC. The 40 A rating at 30 °C derates to 38 A at 40 °C and 37.2 A at 45 °C, so if your panel runs hot, factor that in. The 1P+N pole configuration switches the line and switches the neutral but does not protect the neutral — it's a switched-neutral design, common in single-phase final circuits where you need isolation on both conductors.

Sealable, halogen-free, silicon-free construction suits environments where outgassing matters (clean rooms, medical, food processing). Touch protection is built in, so you don't need separate finger-safe shrouds on the terminals.

Frequently asked questions

What is the breaking capacity of 5SY6040-7?

6 kA per EN 60898 at 230 V AC. That's the standard breaking capacity for this series — suitable for most residential and light commercial final circuits where the prospective short-circuit current stays under 6 kA.

Will 5SY6040-7 drop into a panel specified around 5SY6040-6?

Yes — same 18 mm width, same DIN-rail mounting, same 1P+N pole configuration. The difference is the current rating: 5SY6040-7 is 40 A, while 5SY6040-6 is 6 A. If the panel was wired for 6 A loads, dropping in a 40 A breaker means the cable and downstream devices must be rated for 40 A — the breaker itself fits the same footprint.

How do I get current pricing and availability for 5SY6040-7?

Submit an RFQ through this listing. We source the part through independent distribution and confirm availability and current pricing at quote time — no automated stock count displayed here.