It also carries a 5 kA rating per UL 1077 and CSA C22.2 No.235, so it's accepted in North American panels as a supplementary protector. Depth is 76 mm, height 90 mm.
The 6 kA breaking capacity (EN 60898) is the fault-interruption rating for the AC mains; the 5 kA UL 1077 figure covers supplementary protection in UL-listed panels. The -40 °C to +75 °C operating range covers unheated enclosures and hot cabinet summers.
Snap-on DIN rail mount, 18 mm width (1 MW), any mounting position. Sealable, halogen-free, silicon-free. Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz. Mechanical service life 10,000 operating cycles typical.