Skip to main content
Siemens 5SY6115-8CC — 1-Pole MCB (DIN Rail)

Siemens 5SY6115-8CC SENTRON MCB, 1.6 A D-Curve, 1P, 6 kA

MPN5SY6115-8CC

Siemens SENTRON 5SY6115-8CC, 1-pole miniature circuit breaker, 1.6 A, D characteristic, 400 V AC, 6 kA per EN 60898, 18 mm width, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY6115-8CC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Application suitabilityMechanical engineering / industry
5SY6115-8CC — Electrical & Protection
ParameterValue
Tripping characteristic classD
Rated value (EN 60898)6 kA
Overvoltage categoryIII
5SY6115-8CC — Mounting & Connection
ParameterValue
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
SealableYes
5SY6115-8CC — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SY6115-8CC is a 1-pole SENTRON miniature circuit breaker rated 1.6 A at 400 V AC with a D tripping characteristic. Overvoltage category III means it's rated for fixed-installation distribution panels, not just downstream equipment.

DIN-rail fit and wiring constraints

The 1-pole body takes 76 mm depth behind the panel, with 70 mm installation depth. Torque to 2.5–3.5 N·m. IP20 with conductors connected, so it's panel-internal only — no washdown exposure.

Frequently asked questions

What is the breaking capacity of 5SY6115-8CC?

6 kA per EN 60898 at 400 V AC, and 5 kA per UL 1077 / CSA C22.2 No. 235. The EN rating governs European distribution panels; the UL figure matters for North American installations where the MCB is used as a supplementary protector.

What wire sizes does 5SY6115-8CC accept?

Solid or stranded conductors from 0.75 mm² up to 35 mm². The combined top and bottom screw terminals accept the full range; torque to 2.5–3.5 N·m.

Where can I buy 5SY6115-8CC?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm position.

Will 5SY6115-8CC drop into a panel specified around 5SY6140-6CC without rewiring?

Both are 1-pole SENTRON MCBs on the same 18 mm DIN-rail footprint with identical terminal ranges, so the mechanical swap is direct. The difference is rating: 5SY6115-8CC is 1.6 A D-curve, while 5SY6140-6CC is a higher-current variant with a different characteristic. Verify the load current and trip curve match your circuit before substituting.

MPN
5SY6115-8CC