Siemens 5SY6125-7CC — 1-Pole MCB (DIN Rail)

Siemens 5SY6125-7CC SENTRON MCB, 1P C-curve 25 A, 6 kA

MPN5SY6125-7CC

Siemens SENTRON 5SY6125-7CC, 1-pole miniature circuit breaker, C-curve, 25 A rated, 6 kA breaking capacity per IEC 60898, 5 kA per UL 1077.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY6125-7CC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityMechanical engineering / industry
5SY6125-7CC — Electrical & Protection
ParameterValue
Tripping characteristic classC
Rated value (EN 60898)6 kA
Energy limitation class3
Overvoltage categoryIII
5SY6125-7CC — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY6125-7CC — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

It breaks fault currents up to 6 kA per IEC 60898 and 5 kA per UL 1077 / CSA C22.2 No. 235 — the UL figure is the one to use for North American panel listings.

Derating and ambient conditions — the real-world rating

The 25 A rating holds at 35 °C ambient. Above that the breaker derates: 22.98 A at 40 °C, 21.88 A at 45 °C, 20.72 A at 50 °C, and 19.53 A at 55 °C. If the panel runs hot — say 50 °C inside a sealed cabinet — the continuous load must stay under 20.72 A, not 25 A. The operating range spans -40 to 75 °C, and humidity is capped at 95% up to 55 °C, then 55% up to 70 °C, then 35% up to 75 °C. Vibration resistance per IEC 60068-2-6 is ±1 mm at 5 to 25 Hz and 50 m/s² at 25 to 150 Hz.

The 90 mm height and 18 mm width (1 MW) mean it occupies one slot in a standard distribution board.

Frequently asked questions

What is the breaking capacity of 5SY6125-7CC?

6 kA per IEC 60898 and 5 kA per UL 1077 / CSA C22.2 No. 235. The UL figure governs for North American panel listings; the IEC figure applies for European installations.

What compliance documentation does Siemens provide for 5SY6125-7CC?

The breaker is halogen-free and silicon-free. It carries IEC 60898 and UL 1077 / CSA C22.2 No. 235 certifications. Standard RoHS and REACH declarations are available from Siemens documentation.

Where can I buy 5SY6125-7CC?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time figure is published here.