Siemens 5SY6132-6 SENTRON MCB, 1P B-Curve 32A, 6kA/15kA

MPN5SY6132-6
Active

Siemens SENTRON 5SY6132-6, 1-pole miniature circuit breaker, B-curve, 32 A rated current, 6 kA (EN 60898) / 15 kA (IEC 60947-2) breaking capacity, 1 MW wide, IP20.

$60.91Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY6132-6 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityMechanical engineering / industry
5SY6132-6 — Electrical & Protection
ParameterValue
Tripping characteristic classB
Energy limitation class3
Overvoltage categoryIII
5SY6132-6 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY6132-6 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

Breaking capacity is 6 kA per EN 60898-1 and 15 kA per IEC 60947-2 / UL1077. The dual rating matters: the 6 kA figure is the standard for domestic-style MCBs, but the 15 kA IEC 60947-2 rating is what you need for industrial panels where the prospective fault current can be higher.

Thermal derating — the real-world current you get

The 32 A rating holds at 35 °C ambient. Above that, the thermal-magnetic trip element derates: 30.46 A at 40 °C, 29.66 A at 45 °C, 28.86 A at 50 °C, and 28 A at 55 °C. Factor that into your load calculation so you don't get unexpected trips on a warm day. It's also sealable — you can lock the toggle in the off position for lockout/tagout compliance.

Physical fit and mounting

Dimensions: 18 mm wide, 90 mm high, 76 mm deep. The quick-assembly fastening method is the standard DIN-rail clip — push on, pull off with a screwdriver. IP20 with connected conductors — that's the usual for panel-mounted MCBs. Not for wet locations, but fine inside a rated enclosure. Touch protection is built in (fingertip-safe terminals when wired).

Frequently asked questions

Where can I buy 5SY6132-6 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — no stock count or price is published here.

What is 5SY6132-6's listed depth (76 mm) on this component line?

The depth is 76 mm, with an installation depth of 70 mm. That's the dimension from the DIN-rail mounting surface to the front of the breaker body.

What is 5SY6132-6's listed width (18 mm) on this component line?

Width is 18 mm, which is 1 modular unit (1 MW) on standard DIN rail. It occupies one pole position in a distribution board.

What compliance documentation does this brand provide for 5SY6132-6 (RoHS, REACH, UL, IEC)?

The breaker is certified to IEC / EN 60898-1 and IEC / EN 60947-2 / UL1077. It is halogen-free and silicon-free. Standard Siemens declarations for RoHS and REACH are available on request.

MPN
5SY6132-6