At 32 A, that's a magnetic trip between 320 A and 640 A, so it won't nuisance-trip on a motor start yet clears a hard short fast. Breaking capacity: 6 kA per EN 60898 (the household / commercial standard) and 5 kA per UL 1077 / CSA C22.2 No.235. The 6 kA figure governs in IEC-spec panels; the UL/CSA rating tells you it passes supplementary protection testing for North American installations. IP20 with connected conductors — the busbar and wire terminals are touch-safe once wired, but the breaker itself is not sealed against dust or moisture. Mount it inside a panel with a higher enclosure rating; it's not a standalone outdoor device.
Installation notes
Fastens via quick-assembly system (snap-on DIN rail). Mounting position any — horizontal or vertical in the cabinet is fine. Depth 76 mm, height 90 mm, width 18 mm. Installation depth 70 mm leaves clearance behind the rail.