Siemens 5SY6150-6CC SENTRON MCB, 1P B 50 A, 6 kA

MPN5SY6150-6CC

Siemens SENTRON 5SY6150-6CC, 1-pole miniature circuit breaker, B-characteristic, 50 A rated current, 6 kA breaking capacity per EN 60898, 400 V AC, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY6150-6CC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Application suitabilityMechanical engineering / industry
5SY6150-6CC — Electrical & Protection
ParameterValue
Tripping characteristic classB
Rated value (EN 60898)6 kA
Overvoltage categoryIII
5SY6150-6CC — Mounting & Connection
ParameterValue
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
SealableYes
5SY6150-6CC — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Halogen-freeYes
Silicone-freeYes

Product details

Rated for a 50 A branch — B-curve, 6 kA, 400 V AC

The 50 A rating handles feeder or sub-feeder protection in distribution boards, control panels, and machinery enclosures.

Mounting and integration — 1 width unit, quick-assembly, any position

Occupies 1 width unit (18 mm), depth 76 mm, height 90 mm. The installation depth is 70 mm. Any mounting position is permitted. The combined top and bottom terminals accept solid or stranded conductors from 0.75 to 35 mm²; tighten screw terminals to 2.5–3.5 N·m. Sealable (yes) for tamper-proof isolation.

Environmental and compliance — halogen-free, silicon-free, wide temperature range

Halogen-free and silicon-free construction suits sensitive environments — clean rooms, electronics assembly, or areas where outgassing must be minimized. Humidity tolerance: max 95% at 55 °C, derating at higher temperatures. Overvoltage category III. Energy limiting class 3. The 5SY series carries the 5SY6CC design variant for this specific rating.

Frequently asked questions

Who supplies 5SY6150-6CC and how is it quoted for volume purchases?

This part is sourced through independent industrial-automation distribution. Availability and pricing are confirmed at quote time against an RFQ — submit a request for current lead time and volume pricing.

What is 5SY6150-6CC's listed depth?

The depth is 76 mm (installation depth 70 mm). Width is 18 mm (1 width unit), height 90 mm.

What is 5SY6150-6CC's listed solid conductor range?

The solid conductor cross-section range is 0.75 to 35 mm²; stranded conductors also accept 0.75 to 35 mm².

What compliance documentation does this brand provide for 5SY6150-6CC?

The breaker is rated per EN 60898 (6 kA) and UL 1077 / CSA C22.2 No.235 (5 kA). It is halogen-free and silicon-free. The manufacturer, Siemens, typically provides RoHS and REACH declarations on request.