Skip to main content
Siemens 5SY6150-7 — 1-Pole MCB (DIN Rail)

Siemens 5SY6150-7 SENTRON MCB, C-Curve, 1P, 6/10 kA

MPN5SY6150-7
Active

Siemens SENTRON 5SY6150-7, 1-pole miniature circuit breaker, C-curve, 6 kA (EN 60898) / 10 kA (IEC 60947-2), 1 MW.

$80.14Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY6150-7 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityMechanical engineering / industry
5SY6150-7 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Energy limitation class3
Overvoltage categoryIII
5SY6150-7 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY6150-7 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SY6150-7 is a 1-pole SENTRON miniature circuit breaker with a C-curve trip characteristic — meaning it holds through momentary inrush up to 5–10× rated current before tripping magnetically, which suits it for mixed resistive and moderate inductive loads like contactor coils, small motor starters, and control transformers in a panel. Breaking capacity is dual-rated: 6 kA per EN 60898 and 10 kA per IEC 60947-2, with an additional 15 kA at DC per IEC 60947-2. The DC rating of 15 kA at 60 V (max 72 V) covers control-circuit DC supplies common in 24 VDC panels. The 18 mm width (1 MW) and 76 mm depth let it snap onto a standard DIN rail in any mounting position, with a quick-assembly fastening system.

Integration notes

The surrounding temperature influence table (max 95% RH at 55 °C, derating to 35% at 75 °C) tells you the breaker's thermal trip element will shift slightly at high ambient — factor that into coordination studies if the panel runs hot.

Frequently asked questions

What breaking capacity does it have?

It is dual-rated: 6 kA per EN 60898, 10 kA per IEC 60947-2 at 400 V AC, and 15 kA at DC per IEC 60947-2. For UL 1077 applications it is rated 5 kA.

What certifications does it carry?

It is certified to IEC/EN 60898-1, IEC/EN 60947-2, and UL 1077 / CSA C22.2 No. 235 — covering both IEC and North American markets with one part number.

What is the physical size for panel layout?

Width is 18 mm (1 modular width unit), depth is 76 mm, height is 90 mm. It snaps onto a standard DIN rail with a quick-assembly system.

MPN