At DC per IEC 60947-2 it holds 15 kA, which matters if this breaker lands in a DC bus or battery circuit.
B-curve trips between 3 and 5 times rated current — 189 to 315 A at 63 A. The 63 A rating is the continuous thermal current at 50/60 Hz; at elevated ambient temperature the breaker derates per the influence curve (max 95% RH at 55 °C, dropping to 35% RH at 75 °C). Width is 18 mm — one modular unit on a standard DIN rail. Mounting position any, which simplifies tight gland-plate layouts.