Rated for 400 V AC (multi-phase or single-phase) and 60 V DC, with a maximum DC operating voltage of 72 V. The breaking capacity depends on the standard applied: 6 kA per EN 60898-1, 30 kA per IEC 60947-2, and 5 kA per UL 1077. The overvoltage category is III, and the pollution degree is 3, so it is rated for fixed installations in industrial environments where transient overvoltages are expected.
Mounting and integration notes
The IP20 rating applies only with connected conductors. The combined terminal design at both top and bottom accepts conductors from either side, and the supply cord position is unrestricted. Neutral conductor switching is not provided — this is a 2-pole breaker for line-side switching only. The sealable feature allows padlocking in the OFF position for lockout/tagout compliance.
Halogen-free and silicon-free construction. Energy limitation class 3. Suitable for mechanical engineering and industrial applications per the manufacturer's designation.