The 400 V AC rating (phase-to-phase) suits three-phase panels where the breaker protects a single-phase load across two poles. On the DC side, the 5SY6203-8 is rated 72 V with a 15 kA breaking capacity per IEC 60947-2, and it carries a UL 1077 / CSA C22.2 No.235 listing at 5 kA — useful for North American supplementary protection applications.
Integration and compliance notes
The 5SY6203-8 does not switch the neutral conductor — it is a 2-pole breaker protecting both phase conductors in a single-phase circuit, or two phases in a three-phase system. The ambient temperature influence is specified up to 75 °C with derating; the unit can be installed in any orientation, and the supply cord position is unrestricted.