Skip to main content
Siemens 5SY6206-8CC — 2-Pole MCB (DIN Rail)

Siemens 5SY6206-8CC SENTRON MCB, 2P D 6A, 6kA 400V

MPN5SY6206-8CC

Siemens SENTRON 5SY6 series, miniature circuit breaker (MCB), 2-pole, D tripping characteristic, 6 A rated current, 6 kA breaking capacity at 400 V AC, 2 MW units wide.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY6206-8CC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SY6206-8CC — Electrical
ParameterValue
Number of poles2
5SY6206-8CC — Protection
ParameterValue
Tripping characteristic classD
Overvoltage categoryIII
5SY6206-8CC — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY6206-8CC — Environmental
ParameterValue
Pollution degree3
5SY6206-8CC — Specifications
ParameterValue
At AC rated value400 V
According to EN 60898 rated value6 kA
With single-phase operation at AC rated value440 V

Product details

What the D-curve and 6 kA rating mean for your panel

The D-curve means it tolerates inrush currents 10–20× the rated current before the magnetic trip fires — sized for loads with high starting peaks like small transformers, solenoid valves, or motor starters where a C-curve would nuisance-trip. Under UL 1077 and CSA C22.2 No. 235 it's rated 5 kA, so check your SCCR study if the panel is built to North American code.

Mounting position is any — vertical, horizontal, or upside-down — which helps when you're packing a dense gland plate.

Environmental and compliance range

Halogen-free and silicon-free construction. Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz. Mechanical service life 10,000 operating cycles typical.

Frequently asked questions

Where can I buy 5SY6206-8CC and how is it quoted?

Sourced through independent distribution channels. Quoted to order against an RFQ; current pricing and availability are confirmed at quote time.

What is the closest functional second-source to 5SY6206-8CC?

The 5SY5240-7 is a 2-pole D-curve MCB from the same SENTRON family, but it's a different current rating and breaking capacity. The 5SY6206-8CC will not drop into a panel wired for the 5SY5240-7 without verifying the load and fault current requirements — the footprint is the same 2 MW DIN rail, but the protection settings differ.

What are the key dimensions of 5SY6206-8CC?

Width 36 mm (2 modular units), depth 76 mm, height 90 mm. Installation depth behind the panel is 70 mm.

What compliance documentation does Siemens provide for 5SY6206-8CC?

The breaker carries ratings per EN 60898 (6 kA at 400 V AC) and UL 1077 / CSA C22.2 No. 235 (5 kA). It's halogen-free and silicon-free. Standard Siemens declarations for RoHS and REACH are available on request.

MPN