Siemens 5SY6213-6 — 2-Pole MCB (DIN Rail)

Siemens 5SY6213-6 SENTRON MCB, 2P, 13 A, B-Curve, 6 kA

MPN5SY6213-6
Active

Siemens SENTRON 5SY6 series, miniature circuit breaker, 2-pole, 13 A, B characteristic, 6 kA per EN 60898, 15 kA per IEC 60947-2, 2 MW, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY6213-6 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SY6213-6 — Electrical
ParameterValue
Number of poles2
5SY6213-6 — Protection
ParameterValue
Tripping characteristic classB
Overvoltage categoryIII
5SY6213-6 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY6213-6 — Environmental
ParameterValue
Pollution degree3
5SY6213-6 — Specifications
ParameterValue
Energy Limitation Class3

Product details

Panel integration checklist

Depth 76 mm, height 90 mm, width 36 mm (2 MW). Combined terminals top and bottom — wire both sides without separate feed-through lugs. Sealable, halogen-free, silicon-free. Touch protection integrated. Suitability flagged for mechanical engineering / industry applications.

Frequently asked questions

Where can I buy 5SY6213-6 and how do I get a price?

The 5SY6213-6 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead-time estimate.

What is the breaking capacity of 5SY6213-6?

6 kA per EN 60898 and 15 kA per IEC 60947-2 (AC and DC). Also rated 5 kA per UL 1077 and CSA C22.2 No.235.

What is the temperature derating for 5SY6213-6?

Rated 13 A at 35 °C, 12.05 A at 45 °C, 11.73 A at 50 °C, 11.38 A at 55 °C. Derate further above 55 °C per the published influence curve.

MPN