What this 5SY6 D-curve MCB does on the line
The Siemens 5SY6213-8 is a 2-pole miniature circuit breaker from the SENTRON 5SY6 series, rated 13 A at 400 V AC with a D tripping characteristic — meaning it tolerates the high inrush currents of motor and transformer loads without nuisance tripping, then clears fast on a hard fault.
Depth is 76 mm (installation depth 70 mm), width 36 mm, height 90 mm — fits standard 2-module DIN-rail cutouts. Halogen-free and silicon-free construction.
Approvals and documentation
Rated per EN 60898 (6 kA), IEC 60947-2 (15 kA AC, 15 kA DC at 72 V), and UL 1077 / CSA C22.2 No. 235 (5 kA). Touch protection built in. Sealable terminals top and bottom. Neutral conductor switching is not included — this is a 2-pole breaker for line/load switching, not a 1P+N device.