Skip to main content
Siemens 5SY6232-6 — 2-Pole MCB (DIN Rail)

Siemens 5SY6232-6 SENTRON MCB, 2P B-32A, 6kA/15kA

MPN5SY6232-6
Active

Siemens SENTRON 5SY6232-6, 2-pole miniature circuit breaker, 32 A rated current, tripping characteristic B, breaking capacity 6 kA (EN 60898) / 15 kA (IEC 60947-2), 36 mm width (2 MW).

$24.13Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY6232-6 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SY6232-6 — Electrical
ParameterValue
Number of poles2
5SY6232-6 — Protection
ParameterValue
Tripping characteristic classB
Overvoltage categoryIII
5SY6232-6 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY6232-6 — Environmental
ParameterValue
Pollution degree3
5SY6232-6 — Specifications
ParameterValue
At AC rated value32 A
According to EN 60898 rated value6 kA
With single-phase operation at AC rated value440 V
Energy Limitation Class3

Product details

It carries dual breaking capacities — 6 kA per IEC/EN 60898-1 for general branch-circuit protection, and 15 kA per IEC 60947-2 / UL1077 for industrial panel applications where higher fault current is expected.

At 32 A continuous, the 5SY6232-6 handles a 7 kW resistive load on a 230/400 VAC system. Temperature derating is published: full 32 A up to 35 °C, then 30.46 A at 40 °C, 29.66 A at 45 °C, 28.86 A at 50 °C, and 28 A at 55 °C. The 5SY6232-6 is sealable, halogen-free, and silicon-free — relevant for food-and-bev or pharmaceutical lines where outgassing or contamination is a concern.

Integration notes

Frequently asked questions

Where can I buy 5SY6232-6?

The 5SY6232-6 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of 5SY6232-6?

6 kA per IEC/EN 60898-1 and 15 kA per IEC 60947-2 / UL1077.

What compliance documentation does Siemens provide for 5SY6232-6?

The 5SY6232-6 complies with IEC/EN 60898-1 and IEC/EN 60947-2 / UL1077. It is halogen-free and silicon-free. Standard documentation includes the declaration of conformity and the datasheet.

Will 5SY6232-6 drop into a panel specified around 5SY4116-6CC?

Both are 2-pole SENTRON MCBs on the same DIN-rail footprint, but the 5SY6232-6 is a 32 A B-curve while the 5SY4116-6CC is a 16 A C-curve. The physical fit is identical; the electrical rating and trip characteristic differ — verify the branch-circuit protection requirements before substituting.

MPN
5SY6232-6