Siemens 5SY6232-7CC — 2-Pole MCB (DIN Rail)

Siemens 5SY6232-7CC SENTRON MCB, 2P C-Curve 32A 6kA

MPN5SY6232-7CC

Siemens SENTRON 5SY6232-7CC miniature circuit breaker, 2-pole, C-curve, 32 A rated, 6 kA breaking capacity per EN 60898, 440 V AC, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY6232-7CC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SY6232-7CC — Electrical
ParameterValue
Number of poles2
5SY6232-7CC — Protection
ParameterValue
Tripping characteristic classC
Overvoltage categoryIII
5SY6232-7CC — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY6232-7CC — Environmental
ParameterValue
Pollution degree3
5SY6232-7CC — Specifications
ParameterValue
Energy Limitation Class3

Product details

Siemens SENTRON 5SY6232-7CC — 2-pole C-curve MCB, 32 A, 6 kA

It's a 2-pole unit with a C-curve tripping characteristic, rated 32 A at 40 °C and 6 kA breaking capacity per EN 60898.

Sizing and thermal derating — what the 32 A rating really means

The 32 A rating holds at 35 °C ambient. At 40 °C it derates to 30.08 A; at 45 °C to 29.09 A; at 50 °C to 28.03 A; at 55 °C to 26.94 A. Plan your load accordingly, especially if you're pushing continuous current near the mark. The operating temperature range is -40 to 75 °C, with humidity limits: max 95% up to 55 °C, then derating to 55% at 70 °C and 35% at 75 °C. That's typical for an indoor industrial MCB — no outdoor or condensation-heavy duty without a weatherproof enclosure.

Mounting position any — no derating for sideways or upside-down install. Combined terminals top and bottom, sealable if the panel requires padlocking. Neutral conductor switching is not provided — this is a 2-pole breaker switching both phases, not a 1P+N configuration. The design of pole is 2P, so it's for two live conductors, not a switched neutral.

Frequently asked questions

Where can I buy 5SY6232-7CC and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at that time.

What is the depth and width of 5SY6232-7CC?

Depth is 76 mm, width is 36 mm (2 modular units), height is 90 mm. Installation depth is 70 mm.

Will 5SY6232-7CC drop into a panel specified for 5SY7210-7CC?

Both are 2-pole SENTRON MCBs on the same DIN-rail footprint — same width (36 mm), same mounting method. The key difference is rating: 5SY6232-7CC is 32 A C-curve; 5SY7210-7CC is a 10 A C-curve. If the panel was wired for 10 A, dropping in a 32 A breaker without checking the downstream conductor sizing and load is not safe. Mechanically it fits; electrically verify the branch circuit.

What compliance documentation does the 5SY6232-7CC carry?

The breaker is halogen-free and silicon-free. It meets EN 60898 for breaking capacity (6 kA) and is classified per EN 61346-2 and IEC 81346-2 as function F. Standard IEC/EN certifications apply for a SENTRON MCB; the manufacturer provides RoHS and REACH declarations on request.