Siemens 5SY6232-8 — 2-Pole MCB (DIN Rail)

Siemens 5SY6232-8 SENTRON MCB, 32A D-curve 2-pole, 6kA/15kA

MPN5SY6232-8

Siemens SENTRON 5SY6 series, 5SY6232-8 miniature circuit breaker, 2-pole, D tripping characteristic, 32 A rated current, 6 kA (EN 60898) / 15 kA (IEC 60947-2), 400 V AC.

$62.80Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY6232-8 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SY6232-8 — Electrical
ParameterValue
Number of poles2
5SY6232-8 — Protection
ParameterValue
Tripping characteristic classD
Overvoltage categoryIII
5SY6232-8 — Mechanical
ParameterValue
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY6232-8 — Environmental
ParameterValue
Pollution degree3

Product details

At 32 A rated current (AC) and 400 V, it covers a solid range of 3-phase and single-phase subfeeds in a 400/415 V network. The 5SY6232-8 carries 6 kA per EN 60898 (the domestic/light-commercial standard) and 15 kA per IEC 60947-2 (the industrial standard). For UL-marked panels, it also lists 5 kA under UL 1077 / CSA C22.2 No.235, so verify the available fault current if the job spec requires UL-listed supplementary protectors.

The quick-assembly mounting system (Siemens' tool-free snap-on) and combined top/bottom terminals speed up panel wiring. Mounting position is unrestricted: vertical, horizontal, or inverted, so it doesn't force a specific orientation in a crowded enclosure. IP20 with connected conductors — finger-safe when wired, but not protected against dripping water or dust ingress.

Environmental range and derating

But the breaker's current-carrying capacity derates with temperature and humidity: the spec table shows max 95% RH up to 55 °C, then 55% up to 70 °C, then 35% up to 75 °C.

Frequently asked questions

Will the 5SY6232-8 drop into a panel specified around 5SY3132-6 without rewiring?

Both are 2-pole MCBs on a 36 mm DIN-rail footprint, so the mechanical fit is identical. However, verify the tripping characteristic — if the 5SY3132-6 is a B or C curve and the circuit requires a D curve, the magnetic trip thresholds differ. Also check the breaking capacity matches the panel's fault-current rating. The physical swap is straightforward; the electrical substitution depends on the load and available fault current.

MPN
5SY6232-8