Breaking capacity and fault handling
For DC circuits, the same breaker is rated 15 kA at 72 V DC (IEC 60947-2), and under UL 1077 / CSA C22.2 No. 235 it carries 5 kA at AC.
Mounts via the quick-assembly system in any position, on any DIN rail. Ambient range runs from -40 °C to 75 °C, with humidity derating above 55 °C (max 95% RH at 55 °C, tapering to 35% at 75 °C).