Skip to main content
Siemens 5SY6306-6CC — 3-Pole MCB (DIN Rail)

Siemens 5SY6306-6CC SENTRON MCB, 6A B-Curve 3-Pole, 6kA

MPN5SY6306-6CC

Siemens SENTRON 5SY6306-6CC, miniature circuit breaker, 3-pole, B characteristic, 6 A rated, 6 kA breaking capacity (EN 60898), 5 kA (UL 1077), 3 MW units, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY6306-6CC — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationMechanical engineering / industry
5SY6306-6CC — Protection
ParameterValue
Tripping characteristic (curve)B
Breaking capacity per EN 608986 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Energy limitation class3
Pollution degree3
5SY6306-6CC — Electrical
ParameterValue
Rated current (AC)6 A
Rated voltage (AC, multi-phase)440 V
5SY6306-6CC — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
Combined terminal, topYes
Combined terminal, bottomYes
Fastening methodQuick assembly system
SealableYes
5SY6306-6CC — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperaturemax. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C

Product details

Siemens SENTRON 5SY6306-6CC — 6 A B-Curve MCB, 3-Pole

Breaking capacity is 6 kA per EN 60898 and 5 kA per UL 1077 / CSA C22.2 No. 235. That 6 kA rating covers the vast majority of residential and light commercial panel applications in IEC territories; the 5 kA UL figure means it's accepted in North American branch circuits listed under UL 1077 (supplementary protectors).

The 6 A rating holds at 35 °C ambient. Above that, the thermal element derates: 5.51 A at 40 °C, 5.25 A at 45 °C, 4.97 A at 50 °C, and 4.69 A at 55 °C. The operating temperature range is -40 °C to 75 °C, with humidity limits that step down as temperature rises — up to 95% RH at 55 °C, 55% at 70 °C, and 35% at 75 °C. That covers outdoor enclosures in cold climates and hot attic spaces alike. The IP20 rating (with conductors connected) is standard for a DIN-rail device inside a closed enclosure; it's not meant for washdown environments.

Dimensions are 54 mm wide (3 MW), 90 mm tall, and 76 mm deep. Installation depth is 70 mm.

Frequently asked questions

Where can I buy the 5SY6306-6CC?

The 5SY6306-6CC is sourced to order through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time.

What is the breaking capacity of the 5SY6306-6CC?

The 5SY6306-6CC has a breaking capacity of 6 kA per EN 60898 and 5 kA per UL 1077 / CSA C22.2 No. 235.

What is the width of the 5SY6306-6CC in modular units?

The 5SY6306-6CC is 54 mm wide, which corresponds to 3 modular width units (MW) on a standard DIN rail.

What compliance documentation does the 5SY6306-6CC carry?

The 5SY6306-6CC is certified to EN 60898 and UL 1077 / CSA C22.2 No. 235. It is halogen-free and silicon-free. The SENTRON series generally complies with RoHS and REACH; specific declarations are available with the product documentation.

MPN
5SY6306-6CC