At 10 A rated (35 °C), it handles continuous resistive loads up to that level; the 6 kA breaking capacity per EN 60898 certifies it can safely interrupt fault currents up to 6 kA at 50/60 Hz AC, which covers most commercial and light industrial panelboard applications. Temperature derating is built in: at 40 °C the continuous rating drops to 9.19 A, at 45 °C to 8.75 A, at 50 °C to 8.29 A, and at 55 °C to 7.81 A. The 3-pole design (3 MW) switches all three phases simultaneously, with no neutral pole switching.

Siemens 5SY6310-7CC SENTRON MCB, C-Curve 10A 3P 6kA
Siemens SENTRON 5SY6310-7CC miniature circuit breaker, C-curve, 10 A rated, 3-pole, 6 kA breaking capacity per EN 60898, 3 MW, IP20 with connected conductors.
Specifications
| Parameter | Value |
|---|---|
| Overvoltage category | III |
| Parameter | Value |
|---|---|
| Width | 54 mm |
| Height | 90 mm |
| Depth | 76 mm |
Product details
Frequently asked questions
What is the breaking capacity of 5SY6310-7CC?
The 5SY6310-7CC has a 6 kA breaking capacity rated per EN 60898 at 50/60 Hz AC.
What is the temperature derating for 5SY6310-7CC?
At 35 °C the continuous rating is 10 A; it derates to 9.19 A at 40 °C, 8.75 A at 45 °C, 8.29 A at 50 °C, and 7.81 A at 55 °C.
Where can I buy 5SY6310-7CC?
The 5SY6310-7CC is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.