Siemens 5SY6315-7CC — 3-Pole MCB (DIN Rail)

Siemens SENTRON 5SY6315-7CC MCB, 3P, C-Curve, 1.6 A, 6 kA

MPN5SY6315-7CC

Siemens SENTRON 5SY6315-7CC, 3-pole miniature circuit breaker, C-curve, 1.6 A rated current, 6 kA breaking capacity at 400 V AC per EN 60898, IP20.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

5SY6315-7CC — Identification
ParameterValue
Design / model code5SY6CC
Brand nameSENTRON
Number of poles3
Suitability for operationMechanical engineering / industry

Protection

5SY6315-7CC — Protection
ParameterValue
Tripping characteristic (curve)C
Breaking capacity per EN 608986 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors

Electrical

5SY6315-7CC — Electrical
ParameterValue
Rated current (AC)400 V
Rated voltage (AC, multi-phase)440 V
Rated frequency50/60 Hz

Mechanical

5SY6315-7CC — Mechanical
ParameterValue
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Combined terminal, topYes
Combined terminal, bottomYes
SealableYes

Environmental

5SY6315-7CC — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperaturemax. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C

Product details

Siemens SENTRON 5SY6315-7CC — 3-pole MCB, C-curve, 1.6 A

The Siemens SENTRON 5SY6315-7CC is a 3-pole miniature circuit breaker rated 1.6 A with a C-curve tripping characteristic, designed for branch-circuit protection in industrial control panels and distribution boards. It breaks fault currents up to 6 kA at 400 V AC per EN 60898, and carries a 5 kA interrupting rating under UL 1077 and CSA C22.2 No.235 — so it clears a hard short on a motor branch or lighting circuit without welding its contacts shut. The C-curve (5–10× In) means it tolerates the inrush of small motors, transformers, or capacitive loads without nuisance tripping, while still opening fast on a bolted fault.

Mounting and wiring — panel integration

Snaps onto DIN rail via quick-assembly system; occupies 3 width units (54 mm) and needs 70 mm clearance behind the panel for the 76 mm depth. Wire range accepts 0.75 to 35 mm² solid or stranded copper.

Frequently asked questions

What wire sizes does the 5SY6315-7CC accept?

Solid or stranded copper from 0.75 to 35 mm². Tightening torque is 2.5 to 3.5 N·m.