Breaking capacity and standards
Under UL 1077 and CSA C22.2 No.235 (supplementary protector recognition for North American panels) it carries 5 kA.
Thermal derating and environmental range
The 16 A rating is at a reference ambient of 40 °C. At 45 °C it derates to 14.54 A; at 50 °C to 14.02 A; at 55 °C to 13.47 A. The operating temperature span runs from -40 °C to 75 °C, with humidity limits that step down as temperature rises (95% RH up to 55 °C, 55% at 70 °C, 35% at 75 °C).