Skip to main content
Siemens 5SY6325-6CC — 3-Pole MCB (DIN Rail)

Siemens 5SY6325-6CC SENTRON MCB, 25A 3P B-Curve, 6kA

MPN5SY6325-6CC

Siemens SENTRON 5SY6325-6CC, 3-pole miniature circuit breaker, 25 A, B characteristic, 6 kA breaking capacity per IEC 60898, 3 modular width units.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY6325-6CC — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationMechanical engineering / industry
5SY6325-6CC — Protection
ParameterValue
Tripping characteristic (curve)B
Breaking capacity per EN 608986 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Energy limitation class3
Pollution degree3
5SY6325-6CC — Electrical
ParameterValue
Rated current (AC)25 A
Rated voltage (AC, multi-phase)440 V
5SY6325-6CC — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
Combined terminal, topYes
Combined terminal, bottomYes
Fastening methodQuick assembly system
SealableYes
5SY6325-6CC — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperaturemax. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C

Product details

The 5SY6325-6CC: At 25 A and 6 kA SCCR, this breaker handles branch-circuit protection for lighting, control transformers, and general-purpose loads in a 400 VAC distribution panel. The B curve trips between 3–5× rated current — fast enough for resistive loads and short cable runs, but won't ride through motor inrush like a C or D curve would. If you're feeding a motor starter directly, step up to a C-curve sibling; the B characteristic is better suited to the panel's outgoing lighting and control circuits. Temperature derating is published: at 35 °C it holds full 25 A; at 40 °C it's 23.5 A; at 50 °C it drops to 21.9 A. Mounts in any position.

Halogen-free and silicon-free construction. Sealable for lockout/tagout. IP20 with connected conductors. Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz. Ambient humidity limits: 95% up to 55 °C, 55% up to 70 °C, 35% up to 75 °C.

Frequently asked questions

What is the breaking capacity of 5SY6325-6CC?

6 kA per EN 60898 and 5 kA per UL 1077 / CSA C22.2 No. 235.

Where can I buy 5SY6325-6CC?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

What compliance documentation is available for 5SY6325-6CC?

The breaker carries IEC 60898, UL 1077, and CSA C22.2 No. 235 approvals. Halogen-free and silicon-free. RoHS/REACH declarations are standard with the shipment.

MPN
5SY6325-6CC