Skip to main content
Siemens 5SY6410-7CC — 4-Pole MCB (DIN Rail)

Siemens 5SY6410-7CC SENTRON MCB, 4P C-curve 10 A 6 kA

MPN5SY6410-7CC

Siemens SENTRON, miniature circuit breaker, 4-pole, C-curve, 10 A rated, 6 kA breaking capacity per EN 60898, 4 MW units, IP20, 50/60 Hz AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY6410-7CC — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY6410-7CC — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated voltage, AC (multi-phase)440 V
5SY6410-7CC — Protection
ParameterValue
Tripping characteristic (trip curve)C
Energy limitation class3
Overvoltage categoryIII
Pollution degree3
Degree of protection (IP)IP20, with connected conductors
5SY6410-7CC — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Fastening / mounting methodQuick assembly system
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SY6410-7CC — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
5SY6410-7CC — Performance
ParameterValue
Power loss per pole, AC (hot state, at In)1.1 W

Product details

The Siemens 5SY6410-7CC is a SENTRON 4-pole miniature circuit breaker with a C tripping characteristic, rated 10 A at 35 °C and 6 kA breaking capacity per EN 60898.

If your service entrance has a higher prospective fault current, you'll need a current-limiting upstream breaker or a higher-rated device. Temperature derating is real: at 40 °C the continuous rating drops to 9.4 A, at 50 °C to 8.76 A, and at 55 °C to 8.42 A. IP20 with connected conductors — fine inside a closed cabinet, not for wet or outdoor locations without an enclosure.

The breaker is sealable, halogen-free, and silicon-free — important for food-and-bev or clean-room panels where outgassing can contaminate product. Operating voltage is AC 50/60 Hz; DC operation is limited to 72 V maximum.

Frequently asked questions

What is the breaking capacity of the 5SY6410-7CC?

It is rated 6 kA per EN 60898, which covers typical commercial and light industrial fault currents. For higher fault levels, upstream current-limiting coordination is required.

Where can I buy the 5SY6410-7CC?

We supply it through our independent distribution channel. Submit an RFQ for current pricing and availability — orders are quoted to order, not stocked on the shelf.

Will the 5SY6410-7CC replace a 5SY4140-7 in an existing panel?

Both are 4-pole C-curve SENTRON MCBs on the same DIN-rail footprint (4 MW units, 72 mm wide). The 5SY6410-7CC carries a 10 A rating and 6 kA breaking capacity; the 5SY4140-7 has different ratings. Check your existing coordination study — the physical fit is the same, but the electrical ratings must match the circuit design.

MPN
5SY6410-7CC