Skip to main content
Siemens 5SY6416-8 — 4-Pole MCB (DIN Rail)

Siemens 5SY6416-8 SENTRON MCB, 4P D 16 A, 6/15 kA

MPN5SY6416-8

Siemens SENTRON 5SY6 series, 4-pole miniature circuit breaker, D tripping characteristic, 16 A rated current, 400 V AC, 6 kA (EN 60898) / 15 kA (IEC 60947-2).

$599.53Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY6416-8 — Identification
ParameterValue
Type / order code5SY6
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY6416-8 — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated current (In), AC400 V
Rated current (In), AC16 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, AC (single-phase)440 V
Rated voltage, DC (max.)72 V
Voltage typeAC
Rated frequency50/60 Hz
5SY6416-8 — Protection
ParameterValue
Tripping characteristic (trip curve)D
Rated breaking capacity (Icn), per EN 608986 kA
Rated breaking capacity, per IEC 60947-215 kA
Breaking capacity, AC (UL 1077 / CSA C22.2 No.235)5 kA
Overvoltage categoryIII
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingNo
Touch protectionYes
5SY6416-8 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
SealableYes
5SY6416-8 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
5SY6416-8 — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)10 000

Product details

The Siemens 5SY6416-8 is a 4-pole SENTRON miniature circuit breaker with a D tripping characteristic, rated 16 A at 400 V AC. The D-curve means it tolerates inrush currents up to 10–20× rated current before tripping magnetically — sized for motor, transformer, or welding loads that draw a heavy start surge without nuisance tripping on the branch. Breaking capacity is 6 kA per EN 60898 for general distribution, and 15 kA per IEC 60947-2 for industrial feeder duty; the higher figure gives you coordination headroom in a panel with high prospective fault current. Mounts on DIN rail via the quick-assembly system, occupies 4 width units (72 mm), and accepts conductors from 0.75 to 35 mm² solid or stranded — enough cross-section for the 16 A feed plus downstream tap-offs.

Depth of 76 mm and height of 90 mm fit standard DIN-rail enclosures; the 70 mm installation depth leaves clearance for rear-connected busbars. Ambient range -25 to +55 °C, storage down to -40 °C, with humidity derating above 55 °C.

Frequently asked questions

How do I get current pricing and availability for 5SY6416-8?

Submit an RFQ through this listing. The part is sourced to order via independent distribution; availability and current pricing are confirmed at quote time.

Will 5SY6416-8 drop into a panel that was specified around 5SY4140-7 without rewiring?

The 5SY6416-8 is a 4-pole D-curve 16 A breaker from the SENTRON 5SY6 series; the 5SY4140-7 is a different variant in the same family. Both share the same 4-pole DIN-rail footprint and quick-assembly mounting, so mechanical fit is the same. However, verify the tripping characteristic and breaking capacity against your panel's coordination study — the 5SY6416-8 uses a D-curve (10–20× In magnetic trip) and offers 15 kA per IEC 60947-2, which may differ from the 5SY4140-7's ratings.

What compliance documentation does this brand provide for 5SY6416-8?

The 5SY6416-8 carries approvals per EN 60898 (6 kA) and IEC 60947-2 (15 kA), with UL 1077 and CSA C22.2 No. 235 listing at 5 kA. It is halogen-free and silicon-free. Standard Siemens SENTRON documentation includes CE declaration, RoHS/REACH compliance data, and the product datasheet.

MPN
5SY6416-8