Siemens SENTRON 5SY6450-6 — 50 A, 4-pole, B-curve MCB
It carries a 6 kA breaking capacity per EN 60898-1 and a 10 kA rating per IEC 60947-2 / UL 1077, so it handles fault currents up to those levels without upstream coordination issues.
Derating and ambient conditions
Rated current holds at 50 A up to 35 °C, then steps down: 48 A at 40 °C, 47 A at 45 °C, 45.95 A at 50 °C, and 44.9 A at 55 °C. Humidity limits are 95% up to 55 °C, dropping to 35% at 75 °C; that's fine for most indoor industrial enclosures but not for direct washdown zones.
Mounts in any position — no orientation restrictions for vertical or horizontal DIN-rail layouts. The quick-assembly fastening method clips onto the rail without tools.