The breaker is certified to IEC / EN 60898-1 (6 kA) and IEC / EN 60947-2 (10 kA), plus UL1077 — so it meets both residential and industrial coordination requirements.
The 50 A rating holds at 35 °C ambient; at 40 °C it derates to 48 A, at 45 °C to 47 A, at 50 °C to 45.95 A, and at 55 °C to 44.9 A. That means a panel running at 50 °C loses about 8 % of the nominal current — factor that into your load schedule if the breaker shares a crowded enclosure.
Breaking capacity and DC rating
For DC circuits the breaker is rated 15 kA per IEC 60947-2, which covers many battery-backed or rectifier-fed loads.
Depth is 76 mm (installation depth 70 mm), height 90 mm, width 72 mm (4 MW). The breaker is sealable, halogen-free and silicon-free — important for clean-room or food-bev zones where outgassing contaminants can’t be tolerated.