At DC, it carries a 15 kA interrupting rating per IEC 60947-2 up to 60 V, with a maximum DC voltage of 72 V. That dual-standard certification means the same unit satisfies both wiring-rule (EN 60898-1) and industrial (IEC 60947-2) requirements — useful when a panel must meet both a local code and a machine-builder spec.
Snap-on DIN-rail mounting in any orientation. The 36 mm width occupies 2 modular units on a standard DIN rail — plan for that slot in your panel layout. Neutral conductor switching is built in, so no separate switched-neutral accessory is needed for single-phase final circuits.
Vibration resistance per IEC 60068-2-6 covers ±1 mm at 5–25 Hz and 50 m/s² at 25–150 Hz — adequate for machine-mounted panels on pumps, compressors, and conveyors.