Breaking capacity is 6 kA per EN 60898; under UL 1077 and CSA C22.2 No. 235 it's rated 5 kA, so check your available fault current if the panel ships to a North American site. Current derating is published: 1.88 A at 40 °C ambient, 1.82 A at 45 °C, 1.75 A at 50 °C, 1.68 A at 55 °C. Humidity tolerance follows a stepped curve — 95% RH up to 55 °C, dropping to 35% RH at 75 °C — which governs sealed enclosures in washdown or outdoor cabinets.
That 6 mm difference is the arc chamber clearance — don't compress it against the backplane.